Features
The DSE 10 Amp Switch Mode Battery Charger is designed to be permanently connected to a
battery, keeping it charged to maximum capacity.
The chargers can be mounted to the chassis or panel using the fixing points or optional DIN rail clips.
The charger's stylish design includes two LED indicators on the front to show when the charger is
connected to the mains/utility supply and to indicate when a fault condition occurs.
The charger does not include any moving parts to give added durability and reliability. They will also continue to operate during cranking and running. The charger can also accept multiple voltage connections.
ADVANCED FEATURES
Multi-Stage Intelligent Charging
• Constant current- Maximum current available during charge
recovery phase
• Constant voltage
• Chargers automatically return to float mode when charging is complete
Low Output Ripple
• Makes the chargers ideal for all battery types
Full Protection
• Reverse polarity protection, short circuit protection and current limiting
• Automatic recovery after the removal of fault conditions
Boost Mode
• Boosts and equalises cell charge improving battery performance and life
• Simple boost connection using on-board terminals
Power Save Mode
• Once the battery is fully charged the chargers switch to Eco- Power to save energy
KEY BENEFITS
• Suitable for a wide range of battery types
• No moving parts for longer battery charger life
• Switched mode design
• Charger fail output
• Minimum 80% efficiency throughout full operating range
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT
OUTPUT
10 A DC 12 V DC at 13.7 V DC
RIPPLE AND NOISE
<1%
EFFICIENCY
>80%
REGULATION
LINE
<1% Vo
LOAD
<2% Vo
PROTECTIONS
Short Circuit
Over Current
Reverse Polarity
DIMENSIONS
OVERALL
152 mm x 188 mm x 62 mm
6” x 7.4”x 2.44”
WEIGHT
0.7 kg
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS