This is an obsolete product, no longer available for purchase.
Features
The DSE4210 Auto Start Control Module is suitable for a wide variety of single gen-set applications.
Whilst maintaining functions included within higher end controllers, such as generator or load power monitoring, the DSE42xx range of especially compact controllers provide the user with the ultimate size to feature ratio.
Monitoring engine speed, oil pressure, coolant temperature, frequency, voltage and fuel level, the modules will give comprehensive engine and alternator protection. This will be indicated by the user friendly fault indication by LED.
Non-electronic (alternator sensing) engine support for diesel, gas and petrol engines all in one variant. With a number of flexible inputs, outputs and protections, the modules can be easily adapted to suit a wide range of applications.
Through USB Communication both modules can be easily configured using the DSE Configuration Suite PC Software or can be partially configured through the module's front panel editor.
All DSE products are supported by the DSE global technical support team which gives our customers and end users access to 24 hour system help and advice.
KEY BENEFITS
• Ultimate size to feature ratio
• Hours counter via PC software
• User-friendly set-up and button layout for ease of use
• The module can be configured to suit a wide range of applications
• Uses DSE Configuration Suite PC Software for simplified configuration
• Licence-free PC software
• IP65 rating (with optional gasket) offers increased resistance to water ingress
KEY FEATURES
• User friendly fault indication by LED
• Fully configurable via the fascia or PC using USB communication
• Extremely efficient power save mode
• 3 phase generator sensing
• Compatible with 600 V AC
Ph to Ph nominal systems
• Fuel and start outputs
• 4 configurable DC outputs (2 for DSE4210)
• 7 configurable digital inputs
• Configurable staged loading outputs
• Alternator speed sensing
• 3 engine maintainance alarms
• Engine speed protection
• Engine hours counter
• Engine pre-heat
• Engine run-time scheduler
• Battery voltage monitoring
• Start on low battery voltage
• Configurable remote start input
• 1 alternative configuration
• Comprehensive warning, electrical trip or shutdown protection upon fault condition
• Event log (15)
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 80 mA at 24 V
MAXIMUM STANDBY CURRENT
40 mA at 12 V, 45 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at DC supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at DC supply voltage
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
DIMENSIONS
OVERALL
140 mm x 113 mm x 43 mm
5.5’’ x 4.4” x 1.7”
PANEL CUT-OUT
118 mm x 92 mm
4.6’’ x 3.6”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
STORAGE TEMPERATURE RANGE
-40°C TO +85°C
OPERATING TEMPERATURE RANGE
-30°C TO +70°C
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.