Features
The DSE720 is an Automatic Mains (Utility) Failure Control Module suitable for a wide variety of single diesel or gas genset applications.
Monitoring an advanced list of engine parameters, the DSE720 will automatically shut down the engine, or indicate a warning, on detection of a fault condition, indicating the fault on the module’s front panel LCD display or LED.
The module can be easly configured using the DSE810 interface and PC. Front panel editing is also available.
The module can be controlled from a PC that is located up to a maximum distance of 100 meters
away.
The DSE720 also has the ability to monitor the mains (utility) supply, automatically controlling the
switch-over to generator when the mains (utility) power fails.
KEY FEATURES
• PC/Front panel configuration
• Digital and analogue inputs
• Digital outputs
• Automatic mains (utility) supply
monitoring
• Automatic shutdown or warning
when fault conditions are detected
• Automatic/Manual/Remote start
• Engine pre-heat
• Engine monitoring and protection features
• Protected Solid State (PSS) outputs
• Tamper-proof engine hours counter
• LED indicators
• Configurable timers
• Configurable outputs
• Configurable inputs
• Back-lit character/icon LCD display
KEY BENEFITS
• Automatic transfer between
mains (utility) and generator
power
• On-site module configuration
and remote configuration (max
100 meters) using DSE PC
software
• User-friendly set-up and button
layout
• Multiple engine parameters are
monitored simultaneously
• License-free PC software
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
MAXIMUM OPERATING CURRENT
180 mA at 12 V. 190 mA at 24 V
MAXIMUM STANDBY CURRENT
145 mA at 12 V. 150 mA at 24 V
OUTPUTS
AUXILIARY
Solid state
2.4 A DC at supply voltage
FUEL/START
Solid state
3.4 A DC at supply voltage
GENERATOR C.T.
5 A secondary 0.5 VA
INPUTS
GENERATOR INPUT RANGE
35 V(L-N) to 333 V AC(L-N) absolute maximum
50 Hz - 60 Hz (min 15 V AC)
MAINS (UTILITY) SENSING INPUT
RANGE
35 V(L-N) to 333 V AC (L-N)
50 Hz - 60 Hz (min 15 V AC)
DIMENSIONS
OVERALL
209 mm x 146 mm x 30.3 mm
8.2” x 5.7” x 1.2”
PANEL CUT-OUT
182 mm x 137 mm
7.2” x 5.4”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30° C
BS EN 60068-2-2
Bb/Be Dry Heat +70° C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40° C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.