The DSE4410 Single Phase is an Auto Start Control module for single genset applicaiton. The module has been disigned to work with electronic and non-electronic applications providing advanced monitoring and protection features.
The module is available in CANbus and magnetic pick-up versions (to be specified on ordering)
The module includes a back-lit LCD display which clearly shows the status of the generator at all times. It will monitor frequency, oil pressure, coolant temperature and fuel level. The module has also been designed to display the warning a nd shutdown status of the engine.
The module includes six digital inputs and six outputs. Four outputs are configurable on the magnetic pick-up version and six are configurable on the CANbus version. The module can either be programmed using the front panel or by using the DSE PC Configuration Suite software.
• PC and front panel configurable
• CAN and magnetic pick-up versions
• Six digital inputs/one analogue input
• Six outputs (all six configurable on CANbus version, four configurable on magnetic pick-up version)
• Event log (5)
• 50/60 Hz setting
• Configurable timers
• Automatic shutdown or warning when fault conditions are detected
• Manual and remote start
• Engine pre-heat
• Protected Solid State outputs (PSS)
• Advanced metering capability
• Front panel/PC programming
• Engine hours counter
• LED indication
• Icon LCD display
DC SUPPLY
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the
need for internal batteries. LEDs and backlight will not be maintained during cranking.
INPUTS
GENERATOR INPUT RANGE
15V to 333V AC (L-N) absolute maximum
50Hz - 60Hz (min 15V AC)
CHARGE FAIL/EXCITATION RANGE
0V to 35V
MAGNETIC PICK-UP
VOLTAGE RANGE
0.5V RMS minimum
FREQUENCY RANGE
10,000 Hz (max)
OUTPUTS
OUTPUT A (FUEL)
2 Amp DC at supply voltage
OUTPUT B (START)
2 Amp DC at supply voltage
AUXILIARY OUTPUTS C,D
2 Amp DC at supply voltage
DIMENSIONS
OVERALL
180 mm x 116 mm x 42 mm
7.1” x 4.6” x 1.7”
PANEL CUT-OUT
154mm x 98mm
6” x 3.9”
MAXIMUM PANEL THICKNESS
8mm (0.3”)
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.