Features
The DSE702 is available in Manual and Auto Start versions, offering an excellent range of engine
monitoring and protection features. The module offers inputs to monitor low oil pressure, high engine
temperature and overspeed and the manual start version also has a user-defined auxiliary input. Auto
Start versions also include an input option for a start signal from a remote location.
When the module detects any of the above faults it will automatically shut down the engine.
The module also has the capability to monitor battery charging by utilising the WL terminal on the
charge alternator. On detecting a battery charging fault, it will light the warning LED on the front panel.
The DSE702 also includes a tamper-proof engine hours counter.
KEY FEATURES
• Manual start and Auto Start versions
• Remote start input (auto start version only)
• Auxiliary shutdown input (Manual start version only)
• Engine monitoring and protection
• LED indication
• Engine pre-heat
• Tamper proof engine hours
• Front panel mounting
KEY BENEFITS
• Hours counter provides
accurate information for monitoring maintenance and warranty periods
• Multiple engine parameters are
monitored simultaneously
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.
OUTPUTS
CRANK
Solid state 1.2 A negative grounding terminal
FUEL
Solid state 1.2 A negative grounding terminal
PRE-HEAT
Solid state 1.2 A negative grounding terminal
GENERATOR
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
DIMENSIONS
OVERALL
84 mm x 72 mm x 34.9 mm
3.3” x 2.8” x 1.4”
Excludes key switch
PANEL CUT-OUT
80 mm x 68 mm
3.1” x 2.7”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
OPERATING TEMPERATURE RANGE
-30°C to +70°C
STORAGE TEMPERATURE RANGE
-40°C to +80°C
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30° C
BS EN 60068-2-2
Bb/Be Dry Heat +70° C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three
major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40° C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS