The DSE7420 is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, gen-set applications.  A sophisticated module monitoring an extensive number of engine parameters, the DSE74xx will annunciate warnings, shutdown and engine status information on the back-lit LCD screen, illuminated LED, remote PC, audible alarm and via SMS text alerts. The module includes RS232, RS485 & Ethernet ports as well as dedicated terminals for system expansion.

 

The DSE7400 Series Modules are compatible with electronic (CAN) and non-electronic (magnetic pickup/alternator sensing) engines and offers a comprehensive number of flexible inputs, outputs and
extensive engine protections so the system can be easily adapted to meet the most demanding industry
paralleling requirements.

The modules can be easily configured using the DSE Configuration Suite Software.Selected front panel editing is also available.

Get a Quote

Get a Quote

Image of DSE7420

Main features

KEY FEATURES

  • Configurable inputs (11)
  • Configurable outputs (8)
  • Voltage measurement
  • Mains (utility) failure detection
  • Dedicated load test button
  • kW overload alarms
  • Comprehensive electrical protection
  • RS232, RS485 & Ethernet remote communications
  • Modbus RTU/TCP
  • PLC functionality
  • Multi event exercise timer
  • Back-lit LCD 4-line text display
  • Multiple display languages
  • Automatic start/Manual start
  • Audible alarm
  • Fixed and flexible LED indicators
  • Event log (250)
  • Engine protection
  • Fault condition notification to a designated PC
  • Font panel mounting
  • Protected front panel programming
  • Configurable alarms and timers
  • Configurable start and stop timers
  • Five key menu navigation
  • Front panel editing with PIN protection
     
  • 3 configurable maintenance alarms
  • CAN and Magnetic Pick-up/Alt. sensing
  • Fuel usage monitor and low fuel alarms
  • Charge alternator failure alarm
  • Manual speed control (on compatible CAN engines)
  • Manual fuel pump control
  • “Protections disabled” feature
  • Reverse power protection
  • Power monitoring (kW h, kV Ar, kV A h, kV Ar h)
  • Load switching (load shedding and dummy load outputs)
  • Automatic load transfer
  • Unbalanced load protection
  • Independent Earth Fault trip
  • Fully configurable via DSE
  • Configuration Suite PC software
  • Configurable display languages
  • Remote SCADA monitoring via
  • DSE Configuration Suite PC
  • software
  • Advanced SMS messaging
  • (additional external modem required)
  • Start & stop capability via SMS messaging
  • Additional display screens to help with modem diagnostics
  • DSENet® expansion compatible
  • Integral PLC editor

KEY BENEFITS
• RS232, RS485 & Ethernet can be used at the same time
• DSENet® connection for system expansion
• PLC functionality
• Five step dummy load support
• Five step load shedding support
• High number of inputs and outputs
• Worldwide language support
• Direct USB connection to PC
• Ethernet monitoring
• USB host
• Data logging & trending

Specification

DC SUPPLY
CONTINUOUS VOLTAGE RATING

8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
260 mA at 12 V, 130 mA at 24 V
MAXIMUM STANDBY CURRENT
120 mA at 12 V, 65 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)

15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I & J
2 A DC at supply voltage

 

GENERATOR
VOLTAGE RANGE

15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz


MAINS (UTILITY)

VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICK UP
VOLTAGE RANGE

+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
 

DIMENSIONS
OVERALL

240 mm x 172 mm x 57 mm
9.4” x 6.8” x 2.2”
PANEL CUTOUT
220 mm x 160 mm
8.7” x 6.3”
MAXIMUM PANEL THICKNESS
8 mm
0.3”

STORAGE TEMPERATURE RANGE
-40 oC to +85 oC

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY

BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY

BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATURE

BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

HUMIDITY

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours

SHOCK

BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES

BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.