Deep Sea Electronics

DSEDse-genset

DSE7120

Auto Mains (Utility) Failure Control Module

Features

The DSE7120 has now been superseded by the DSE7120 MKII, please see associated products.

 

The DSE7120 is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, genset applications.

Monitoring speed, frequency, voltage, current, oil pressure, coolant temperature and fuel level, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen and illuminated LEDs.

The module offers electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engine versions and offer an extensive number of flexible inputs, outputs and advanced engine protections so the system can be easily adapted to suit a wide range of application demands.

Enhanced features include a realtime clock for improved event monitoring and a 4-line icon display.

The modules can be easily configured using the DSE Configuration Suite PC software.  Front panel editing is also available.

Get a Quote

add another product
remove product
Image of DSE7120

Main features

KEY FEATURES

• Back-lit icon LCD display
• Five key menu navigation
• Front panel editing
• LED and LCD alarm indication
• Power Save mode
• 4 Digital inputs
• 3 Analogue inputs (2 fixed, 1 flexible)
• 6 configurable outputs
• Configurable timers and alarms
• Alternative configuration
• Event Log (5)
• CAN and Magnetic Pick up / Alt. sensing
• 3 Phase generator monitoring
• Current monitoring and protection

 

• 3 Phase Mains (Utility) monitoring
• Test button
• Automatic load transfer
• Battery voltage monitoring
• Engine pre-heat
• Hours counter
• Comprehensive shutdown or warning on fault condition
• Backed-up real-time clock
• Fully configurable via DSE Configuration Suite PC software
• USB connectivity
• Remote SCADA monitoring via DSE Configuration Suite PC software

KEY BENEFITS

• Automatically transfers between
mains (utility) and generator power
• Real-time clock provides accurate event logging
• Hours counter provides accurate information for monitoring and maintenance periods
• User-friendly set-up and button layout
• Multiple engine parameters are monitored simultaneously
• Module can be configured to suit individual applications
• Compatible with a wide range
of CAN engines
• Uses DSE Configuration Suite
PC software for simplified configuration
• IP65 rating (with supplied gasket) offers increased resistance to water ingress
• Licence-free software

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING

8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries.  LEDs and backlight will not be maintained during cranking.

MAXIMUM OPERATING CURRENT
290 mA at 12 V, 140 mA at 24 V

MAXIMUM STANDBY CURRENT
75 mA at 12 V, 40 mA at 24 V

CHARGE FAIL/EXCITATION RANGE
0 V to 35 V

MAINS (UTILITY)

VOLTAGE RANGE
15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS

OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A 250 V (Volt free)

AUXILIARY OUTPUTS E, F, G & H
2 A DC at supply voltage

GENERATOR

VOLTAGE RANGE

15 V - 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz


MAGNETIC PICK-UP

VOLTAGE RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)

DIMENSIONS


OVERALL
240 mm x 181 mm x 42 mm
9.4” x 7.1” x 1.6”

PANEL CUT-OUT
220 mm x 160 mm
8.7” x 6.3”

MAXIMUM PANEL THICKNESS
8 mm
0.3”

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY

BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY

BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATURE

BS EN 60068-2-1
Ab/Ae Cold Test -30° C
BS EN 60068-2-2
Bb/Be Dry Heat +70° C

VIBRATION

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

HUMIDITY

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40° C
@ 93% RH 48 Hours

SHOCK

BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES


BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.