Features
The DSE6120 is an Auto Mains (Utility) Failure Control Module suitable for a wide variety of single gen-set applications.
Monitoring speed, frequency, voltage, current, oil pressure, coolant temperature and fuel level, the modules will display warnings, shutdown and engine status information on the back-lit LCD screen and illuminated LED.
The module offers electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engine versions and a number of flexible inputs, outputs and engine protections so the system can be easily adapted to suit a wide range of application demands.
The module can be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.
KEY FEATURES
• Back-lit text LCD display
• Front panel editing
• LED and LCD alarm indication
• Power Save mode
• CAN and Magnetic Pick-up/Alt.
versions available (specify on ordering)
• PC and front panel configuration
• 6 Digital inputs
• 3 Analogue inputs
• 6 Outputs (4 configurable on Magnetic Pick-up/Alt., 6 configurable on CAN version)
• Configurable timers and alarms
• Alternative configuration
• Event Log (10)
• Remote Start input
• 3 Phase generator monitoring
• Current Monitoring and protection
• 3 Phase Mains (Utility) monitoring
• Test button
• Battery voltage monitoring
• Engine pre-heat
• Hours counter
• Comprehensive shutdown or warning on fault condition
KEY BENEFITS
• Automatically transfers between
mains (utility) and generator power
• Hours counter provides accurate
information for monitoring and
maintenance periods
• User-friendly set-up and button layout
• Multiple engine parameters are monitored simultaneously
• Module can be configured to suit individual applications
• Compatible with a wide range of CAN engines
• Uses DSE Configuration Suite PC software for simplified configuration
• IP65 rating (with optional gasket) offers increased resistance to water ingress
• Licence-free PC software
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be aintained
during cranking.
MAXIMUM OPERATING CURRENT
178 mA at 12 V, 95 mA at 24 V
MAXIMUM STANDBY CURRENT
88 mA at 12 V, 50 mA at 24 V
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
2 A DC at supply voltage
OUTPUT B (START)
2 A DC at supply voltage
AUXILIARY OUTPUTS C,D,E & F
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V - 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
DIMENSIONS
OVERALL
215 mm x 158 mm x 42 mm
8.5” x 6.2” x 1.6”
PANEL CUT-OUT
182 mm x 137 mm
7.2” x 5.4”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C
BS EN 60068-2-2
Bb/Be Dry Heat +70°C
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three
major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40° C
@ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three Major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.