DSE125

MSC Converter

The DSE125 MSC Converter module is used to interface an MSC link containing DSE55XX and DSE75XX modules with an MSC link containing DSE8XXX series modules.

It achieves this by providing an MSC link input for the DSE55XX and DSE75XX modules and another for the DSE8XXX series.  This reduces the MSC link functionality of a system to that containing only DSE55XX and DSE75XX modules.

 

3 red LEDs provide indication of the module’s operational status.
 

Image of DSE125

Main features

KEY FEATURES

• Makes the DSE55XX/75XX MSC link compatible with the DSE8XXX
 

KEY BENEFITS

• Makes the DSE55XX/75XX MSC link compatible with the DSE8XXX

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING

8 V to 35 V continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS providing the supply was at least 10 V before the dropout and recovers to 5 V afterwards.

MAXIMUM OPERATING CURRENT
130 mA at 12 V, 70 mA at 24 V

MAXIMUM STANDBY CURRENT
65 mA at 12 V, 35 mA at 24 V
 

DIMENSIONS

134 mm x 76 mm x 49 mm

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY

BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY

BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATURE

BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

HUMIDITY

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours

SHOCK

BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES

BS EN 60529
IP Rating IP21