Deep Sea Electronics

DSEDse-ats

DSE4130

Auto Transfer Switch Control Module

Features

The DSE4130 is an Automatic Transfer Switch controller for genset and other applications. The module will monitor the voltage and frequency of the incoming AC mains (utility) supply and in the event of a failure, will issue a start command to the generator control system.
 

Once the generator is available and producing an output within limits, the DSE4130 will control the transfer device and switch the load from the mains (utility) to the generating set.  Once the mains (utility) supply returns to within limits, the module will command a return to the mains (utility) supply and shut down the generator after a suitable cooling run. Various timing sequences are available to prevent nuisance starting on minor supply breaks.  The module can be easily configured via the front panel.
 

Image of DSE4130

Main features

KEY FEATURES

• Automatic mains (utility) supply monitoring
• Load changeover control
• Manual start
• Protected Solid State (PSS) outputs
• Front panel mounting
• Front panel programming
• LED indicators
• Configurable timers
• Single/three phase mains (utility) sensing
• Remote start input

KEY BENEFITS

• Transfers between mains (utility) and generator power
• On-site module configuration to match user requirements
 

Specification

DC SUPPLY

CONTINUOUS VOLTAGE RATING
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V. This is achieved without the need for internal batteries.

MAXIMUM OPERATING CURRENT
50mA

MAXIMUM STANDBY CURRENT
50mA

ALTERNATOR INPUT RANGE
75V(L-N) to 333V AC (L-N) absolute
maximum

ALTERNATOR INPUT FREQUENCY
50Hz – 60Hz at rated engine speed
(minimum:75V AC L-N)
 

OUTPUTS

START & RUN OUTPUTS
1.2 Amp DC at supply voltage. Switches to battery negative when active

CLOSE GEN/MAINS (UTILITY)
CONTROL OUTPUTS

1.2 Amp DC at supply voltage. Switches to battery negative when active

AUXILIARY OUTPUTS
1.2 Amp DC at supply voltage. Switches to battery negative when active

DIMENSIONS

DSE4130 OVERALL
171mm x 115mm x 49mm
6.75’’ x 4.5’’ x 2’’

DSE4130 CUT-OUT
154mm x 98mm
6.1” x 3.9”
 

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY

BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY

BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATURE

BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

HUMIDITY

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours

SHOCK

BS EN 60068-2-7
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES

BS EN 60529
IP65 - Front of module when installed into the control panel with the sealing gasket (to be ordered seperately)

Associated products