Deep Sea Electronics

DSEDse-ats

DSE335

Automatic Transfer Switch Controller

Features

NEW & IMPROVED

The DSE335 is an Automatic Transfer Switch Controller. The DSE335 monitors the voltage and frequency of the incoming AC supply from two different sources, either generator or mains (utility), or a combination of both. The module monitors S1 (source 1) and in the event of a failure issues a start command to S2 (source 2).

Once S2 is available and producing an output within limits, the module controls the transfer device and switches the load from S1 to S2.  Once the S1 supply returns to within limits, the module commands a load return to S1
and shuts down S2.

Various timing sequences are available to prevent nuisance starting on minor supply breaks.

 

The DSE335 supports many topologies and features include mains (utility) rated volt-free relays, a clear back-lit LCD 4-line text display, showing system status and warnings and red and green LEDs indicating operational status.

The module includes USB, RS232 and RS485 ports as well as dedicated DSENet® terminals for system expansion, this gives features such as remote PC monitoring and SMS text alerts (with external modem).

The module is easily configured using the DSE Configuration Suite PC Software. Selected front panel editing is also available.

Configurable inputs and outputs make the DSE335 fully flexible to suit a wide variety of applications.

When there is no DC supply, a compatible self-seeking power supply is available (DSE160).

Get a Quote

add another product
remove product
Image of DSE335

Main features

KEY FEATURES
• Configurable inputs (12)
• Configurable volt-free outputs (6)
• Configurable DC outputs (6)
• 4-Line back-lit LCD text display
• Five key menu navigation
• Front panel editing with PIN protection
• LED and LCD alarm indication
• Check sync feature
• Passive closed transition
• Remote monitoring
• Source 1/Source 2 control
• 1 A & 5 A CT secondary support
• Phase rotation detection
• Start inhibit
• Load inhibit
• Manual restore to S1
• Supports multiple topologies
• Automatic switch-over between supplies
• Rotary ATS configuration
• Configurable timers and alarms
• Multiple date and time scheduler
• Power monitoring (kW h, kV Ar, kV A h, kV Ar h)

• Load switching (load shedding outputs)
• USB connectivity
• Backed up real time clock
• Fully configurable via DSE Configuration Suite PC software
• Configurable display languages
• User selectable RS232 and RS485 communications
• Configurable Gencomm pages
• SMS messaging (additional external modem required)
• Additional display screens to help with modem diagnostics
• DSENet® expansion compatible
• Integral PLC editor
• Adjustable Modbus inter-frame delay

KEY BENEFITS
• Source 1/Source 2 provides total flexibility for the application of the product
• Fully automatic and switch-over control minimises the effects of power disruptions
• User friendly set-up and button layout
• 3 phase display and check sync provide enhanced module functionality
• DSEWebNet compatible
• DSE Configuration Suite PC Software compatability for remote control and monitoring
• 132 x 64 pixel ratio display for clarity
• Real-time clock provides accurate event logging
• Ethernet communications (via DSE855 module), provides advanced remote monitoring at low cost
• Modules are able to be integrated into building management systems (BMS)
• Increased input and output expansion capability via DSENet®
• Licence-free PC software
• IP65 rating (with supplied gasket) offers increased resistance to water ingress
• 200 node PLC editor allows user configurable functions to meet specific application requirements
• PLC monitoring via SCADA
 

Specification

DC SUPPLY
CONTINUOUS VOLTAGE RATING

8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
480 mA at 12 V, 360 mA at 24 V
MAXIMUM STANDBY CURRENT
126 mA at 12 V, 96 mA at 24 VS1

S1
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
 

OUTPUTS
OUTPUTS A & E

Normally closed volt-free output
8 A AC at 250 V AC
OUTPUTS B & F
Normally open volt-free output
8 A AC at 250 V AC
OUTPUT C & D
Changeover volt-free output
8 A AC at 250 V AC
AUXILIARY OUTPUTS G,H,I,J,K & L
2 A DC at supply voltage

S2
VOLTAGE RANGE

15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz

DIMENSIONS
OVERALL
240 mm x 181 mm x 42 mm
9.4” x 7.1” x 1.6”
PANEL CUT-OUT
220 mm x 160 mm
8.7” x 6.3”
MAXIMUM PANEL THICKNESS
8 mm
0.3”

OPERATING TEMPERATURE RANGE
-30 °C to +70 °C
-22 °F  to +158 °F

STORAGE TEMPERATURE RANGE
-40 °C to +80 °C
-40 °F to +176 °C

Environmental Testing Standards

ELECTRO-MAGNETIC COMPATIBILITY

BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY

BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATURE

BS EN 60068-2-1
Ab/Ae Cold Test -30 °C
BS EN 60068-2-2
Bb/Be Dry Heat +70 °C

VIBRATION

BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

HUMIDITY

BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C
@ 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 °C
@ 93% RH 48 Hours

SHOCK

BS EN 60068-2-7
Three shocks in each of three major axes 15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES

BS EN 60529
IP65 - Front of module when installed into the control panel with the supplied sealing gasket.